Description

Designed for use with the WiNG-MGR and BMS-WING systems, the WiNG-THRM allows you to place a temperature sensor in an environment that may be unfriendly to a wireless transmission – in ductwork, in wells, in pipes, or in refrigerators and freezers – while the transmitter portion of the sensor remains outside that environment, sending the temperature reading back to the WiNG controller.

The WiNG-THRM Features:

  • Uses 900MHz radio-based communication
  • Proprietary wireless design
  • Accepts one 10K-2 thermistor input (12-bit A/D conversion)
  • Designed with your facility’s security in mind, WiNG sensors do not have IP addresses and cannot connect to a Wi-Fi network. This ensures that they cannot be used as unauthorized wireless access points.
  • A transmission range between manager and sensors that is second to none:
    • Up to 100 feet (30.5m) through multiple walls
    • Up to 270 feet (82.3m) through one wall
    • Up to 600 feet (183m) direct line of sight
    • Add up to 1,000 feet (305m) direct line of sight with a WiNG-RXT range extender
  • Unparalleled sensor battery life:
    • Up to 5 years across full operating range: -13°F to 185°F (-25°C to 85°C)
    • Up 8 years at temperatures up to 122°F (50°C)
    • Up to 12 year battery life at room temperature
  • Polling rate of 10-20 seconds

Product Documentation Links

Technical Resources

Frequency

900MHz, 868MHz

Power

  • 3.6V AA lithium battery

Battery Life

  • Up to 5 years when system spans full operating temperature range
  • Up to 8 years at room temperatures up to 122°F (50°C)
  • Up to 12 years at room temperature

Shelf Life

  • 10 years in quiescent mode with battery installed

Transmission

  • Interval: 10-20 seconds (random)
  • Frequency: 900MHz
  • Range: Up to 600 ft line of sight

Thermistor Input

  • Accepts one 10K-2 thermistor input (12-bit A/D conversion)
  • Thermistor must be purchased separately and is not included with purchase of WiNG-THRM sensor

Operating Environment

  • Temperature: -13ºF to 185ºF (-25ºC – 85ºC)
  • Humidity: 0% to 90% RH (Non-condensing)
  • Altitude: -200 ft to 15,000 ft (-70m to 4572m)

Mounting

  • Free standing
  • Zip ties
  • Screw and keyhole – spaced 2.5″ (6.4cm)
  • Junction box – 2 screws spaced 3.28″ (8.3cm)

Dimensions and Weight

  • 4.4″L x 2.5″W x 1.5″H (11.2cmL x 6.4cmW x 3.8cmH)
  • 0.2lb (0.10kg)

Certifications and Standards

  • CE UL61010
  • CSA 22.2 #61010
  • IEC 61326-1
  • FCC 47CFR 15B
  • IC ICES-003
  • EN 61000-3-2
  • EN61000-3-3
  • ETSI EN 301 489-1
  • ETSI EN 301 489-3
  • FCC ID: X7J-A11072401
  • IC: 8975A-A11072401
Copyright 2026 Parameter