Website Preloader

Description

DCM6-L-IECEx is an IECEx-compliant Data Collection Module purpose-built for monitoring battery systems installed in hazardous (Zone 1) environments. The module is intended for use as part of the Cellwatch Battery Monitoring System and Cellwatch Frontier Battery Monitoring System, providing voltage, ohmic, and temperature measurements while meeting explosion
protection requirements for hydrogen and other IIC gas groups.

The DCM6-L-IECEx is intended for use in battery monitoring applications where equipment must be installed within hazardous locations, including:

  • Battery systems located in Zone 1 or Zone 2 hazardous environments.
  • Facilities requiring IECEx / ATEX / UKEX compliance.
  • Applications involving hydrogen or equivalent IIC gas group environments.

Key Features:

  • No critical maintenance or calibration required following installation.
  • All Data Collection Modules come fully integrated with cables and temperature probes.
    • Reduces installation time.
    • No additional integration or certification required
    • No bulky, heavy enclosures.
    • No additional purchases or assembly required.
  • Securely affixed to the battery system to ensure consistent measurement.
    • Can be replaced without opening battery connections.
    • Can also be easily removed for battery replacement.
  • Provides high resolution (1µ) measurements for low-ohmic value cells (2V VLA or NiCad).
  • Highly effective Graphical User Interface.
    • Provides integrated web server.
    • Integrated design wizard.
  • Minimal maintenance, if any for the installed product.
  • Optimally sized for rack mount or wall mount.

Product Documentation Links

 

Technical Resources

Included Equipment:

  • Battery Monitoring Data Collection Module
  • 4 battery monitoring leads
  • 2 power leads
  • Temperature probes
  • Ex-Rated terminal quick connections

Additional Requirements:

  • Battery Monitoring Controller (Frontier Unit, Thermal Runaway Controller, Control Unit)
    • Must be secured behind the Intrinsic Safety Barrier.
  • Integrated Battery Monitoring Unit (iBMU)
    • Must be secured behind the Intrinsic Safety Barrier.

Product Variations:

  • Leads
    • 36-inch leads
    • 72-inch leads
  • Temperature Probes
    • With temp probes
    • Without temp probes
  • Mounting
    • With DIN rail
    • Without DIN rail

Certifications:

  • Zone 1 Explosion proof
    • ATEX AEx mb IIC T4 Gb
    • IECEx Ex mb IIC T4 Gb
    • UKEX II 2G Ex mb IIC T4 Gb
  • Temperature Range
    • 0 ͦC ≤ Tamb ≤ +60 ͦC
  • Safety
    • IEC 61010 – 1, UL 60079-0, UL 60079-18, CSA C22.2 61010-1-12, CSA C22.22 60079-0, CSA C22.2 60079-18
  • CE / UKCA EMC Immunity
    • EN 61326 – 1:2015
  • CE / UKCA EMC Emissions
    • EN55011:2009 + A1:2010 FCC part 15 Sub part B:2019

 

Power:

  • Full Functionality
    • 4–12 VDC
    • 3–12 VDC
  • Limited Functionality (Voltage & Temperature only)

Critical Distances:

  • 75 ft for TP and CT cables through the Intrinsic Safety Barrier.​
  • 100 ft per segment for Fiber Optic maximum distance